An office building requires an average heating power of during winter

PHYSICS · Multi-part · A Level · Physics · Engineering physics · Engineering physics

Problem

An office building requires an average heating power of 15 kW15\,\text{kW} during winter. Two alternatives are considered: • Option A: an electrical resistance heater with 100%100\% efficiency; • Option B: a heat pump that operates between outdoor air at 275 K275\,\text{K} and indoor air at 295 K295\,\text{K} and follows the reversible limit. (i) Calculate the coefficient of performance of the heat pump under the given temperature conditions. (ii) Using the relation obtained in Question 4, state what its COP would be if the same unit were run as a refrigerator between the same reservoirs. (iii) Determine the electrical power input required for Option B to meet the 15 kW15\,\text{kW} heating demand. (iv) Compare the monthly electrical energy consumption (in kWh) for Options A and B if the system runs 1010 hours per day for 3030 days, and compute the percentage saving achieved with the heat pump. (v) Discuss briefly one economic and one environmental advantage of choosing Option B on the basis of your calculations.