A heat pump keeps a room at 293K by delivering 2.0×107J of heat to the room every hour. The outdoor temperature is 273K. If the device operates at 40% of the maximum possible COP for these temperatures, the electrical power input required is closest to
(a) 0.63kW
(b) 3.4kW
(c) 0.95kW
(d) 1.4kW