A three-phase feeder (rms line voltage) carries a balanced rms line current of to a…
PHYSICS · Multi-part · Fermi University Physics · Electricity, Magnetism & Electromagnetism · Earth, Climate & Energy Physics · Electromagnetic induction and alternating-current circuits
Energy from Physics, Ch The grid with variable renewables: power flow, inertia, adequacy and electrification
Problem
A 33kV three-phase feeder (rms line voltage) carries a balanced rms line current of 400A to a load at power factor 0.85 lagging.
((a)) Find the three-phase real power P, reactive power Q and apparent power S the load takes.
((b)) Capacitors at the load correct the power factor to 1 with the real power unchanged. Find the new line current and the fraction by which the feeder's resistive loss falls.