A national system with nominal frequency has synchronised kinetic energy

PHYSICS · Multi-part · Fermi University Physics · Earth, Climate & Energy Physics · Energy systems, storage and demand · Energy systems, storage and demand

Energy from Physics, Ch The grid with variable renewables: power flow, inertia, adequacy and electrification

Problem

A national system with nominal frequency f0=50 Hzf_0=50\,\mathrm{Hz} has synchronised kinetic energy Ek=120 GW sE_k=120\,\mathrm{GW\,s}. It suddenly loses its largest single infeed, ΔP=1.2 GW\Delta P=1.2\,\mathrm{GW}, and frequency response ramps in linearly over Tr=5 sT_r=5\,\mathrm{s}. ((a)) Estimate the frequency nadir, using Δfnadir=f0ΔPTr/(4Ek)\Delta f_{\rm nadir}=f_0\Delta PT_r/(4E_k). ((b)) Three generating units of rated real power 500 MW500\,\mathrm{MW}, 800 MW800\,\mathrm{MW} and 1200 MW1200\,\mathrm{MW} all have droop R=0.05R=0.05. Using the frequency fall found in part (a) as the drop each unit responds to, estimate the extra power each supplies, from ΔPi/Prated,i=−(Δf/f0)/R\Delta P_i/P_{{\rm rated},i}=-(\Delta f/f_0)/R. ((c)) On the same evening, the system must also carry a new electrified winter peak from 88 million homes needing 5 kW5\,\mathrm{kW} of heat each at the design outdoor temperature (heat-pump coefficient of performance 2.42.4 there, all homes heating at once) and 55 million electric cars charging at 7 kW7\,\mathrm{kW} each with a coincidence factor of 0.30.3. Estimate the total added peak power from these two electrified loads.