Three-phase phasor diagrams
A three-phase generator does not produce one alternating voltage — it produces three, each identical in size and frequency but staggered apart in time. Trying to reason about such a system with sine-wave graphs quickly turns messy: three overlapping waveforms, six sign changes, and a headache. Phasor diagrams cut through that mess. By freezing each sinusoid as a rotating arrow at one instant, the whole three-phase source collapses into three arrows spaced apart, and every relationship you need — line voltage from phase voltage in a star connection, line current from phase current in a delta connection, load current shifted by the impedance angle — becomes a picture you can draw with a ruler and protractor rather than an equation you must re-derive each time. This article builds that picture, shows the one geometric rule ( magnitude, rotation) that governs both star and delta, and works it through numerically so the pattern sticks.
A three-phase phasor diagram represents balanced phase quantities as three RMS-magnitude arrows apart, and subtracting any two of them — the operation behind both star line voltages and delta line currents — always produces a resultant times as large, rotated from the phasor being subtracted from.
The core idea
A phasor diagram plots the phase quantities — voltages or currents — as vectors of fixed RMS magnitude, rotating together at the supply frequency but drawn frozen at one instant so only their relative angles matter. For a balanced source with phase sequence R-Y-B, the three phase-voltage phasors sit apart:
where: is the RMS phase voltage (the same for all three, by the balanced assumption), and the angles are measured from taken as the reference. Because the three phasors are equal in magnitude and evenly spaced, they sum to zero — — which is the phasor statement of "no neutral current flows in a balanced star load."
Star connection — line voltage from phase voltage. The voltage between any two line terminals is the phasor difference of the two phase voltages meeting there, e.g. . Graphically this means reversing (rotate it ) and adding it head-to-tail onto ; the resultant lies ahead of and is times as long. Repeating the construction for and produces a second, larger equilateral triangle of line voltages, rotated ahead of the phase-voltage star.
Delta connection — line current from phase current. The same subtraction rule applies to currents in a delta-connected source or load. With phase (winding) currents each apart, the current in a line conductor is the phasor difference of the two winding currents meeting at that junction, e.g. . By the identical geometry, each line current has magnitude and lags the corresponding phase current by .
Load current phasors. For a balanced load of impedance angle (lagging for an inductive load, leading for a capacitive one), each phase current is displaced by from its own phase voltage: lags or leads by , and likewise for Y and B, with the mutual spacing between the three currents preserved. This is simply the familiar single-phase R-L-C phasor relationship applied independently, phase by phase. The one rule to memorise covers both cases: subtracting two equal-magnitude phasors that are apart always yields a resultant of magnitude times the original, rotated from the phasor being subtracted from. In star, this rule acts on voltages (phase voltage to line voltage); in delta, it acts on currents (phase current to line current) — the two connections are mirror images of each other in this respect, and mixing them up is the single most common exam slip.
The goal is to show, starting only from the three balanced phase-voltage phasors written in complex (rectangular) form, that any line voltage formed by subtracting two adjacent phase voltages has magnitude exactly times the phase voltage and leads the "from" phasor by exactly — the single fact that generates every star line-voltage and delta line-current relationship in this topic.
Step 1. Write the two phase voltages involved in complex form, taking as reference: , and .
Step 2. Subtract as instructed by the subscript order, . Substituting, . The real part has grown to and an imaginary part of has appeared purely from the geometry of the spacing.
Step 3. Convert this rectangular result to polar form to read off magnitude and angle. The magnitude is , and the angle is . Both numbers are independent of — they depend only on the spacing, which is why the -and- rule is universal for any balanced three-phase set, not just this particular pair.
Step 4. Generalise by symmetry. The identical algebra applied to and gives magnitude in each case, each leading its own "from" phasor by ; the same steps applied to delta winding currents (replace with and note the subtraction direction that defines a line current) give magnitude , this time lagging by because the line current is defined as (incoming winding current) minus (outgoing winding current) rather than the other way round. The single complex-number calculation above is therefore the engine behind in star and in delta.
Worked example
A balanced star source has RMS, phase sequence R-Y-B, with taken as reference. Find all three line voltages , , using phasor subtraction, and confirm they sum to zero.
Step 1. Write the phase voltages in rectangular form. , , and .
Step 2. Compute , giving at — exactly the predicted by the derivation above.
Step 3. Compute , which is — again magnitude , and ahead of (at ), since .
Step 4. Compute , which is , again ahead of (at ), since . Adding all three: . The three line voltages, each of magnitude at , sum to zero — confirming they form a closed equilateral triangle, exactly as three balanced phasors must.
Competitive stretch
For the same source feeding a balanced star-connected inductive load with lagging and , the load current is . Comparing this to from Step 2, the angle between the line voltage and the phase current is — this relationship, rather than the plain between phase voltage and phase current, is what the two-wattmeter power-measurement method relies on.
Common traps
- Drawing the line-voltage triangle as a simple "stretched" copy of the phase-voltage star without the rotation — both the scaling and the shift must appear together.
- Getting the subtraction order backwards: , not ; the subscript order fixes which phasor is reversed and added.
- Assuming the load current always sits from the phase voltage — that belongs to the star/delta geometric transformation; the load's own current-to-phase-voltage angle is the impedance angle , which depends entirely on the load.
- Mixing up which quantity picks up the / transformation in each connection — voltages transform this way in star (phase voltage to line voltage); currents transform this way in delta (phase current to line current).
Ask the tutor: want to practice constructing the full phasor diagram for a specific lagging or leading power-factor load, step by step?
Why does the line voltage end up root 3 times the phase voltage instead of just twice as much?
Because the two phase voltages being subtracted are not in phase or exactly opposite — they are apart. If they were opposite ( apart) the difference would indeed be twice as large; if in phase, the difference would be zero. At apart, the vector-triangle geometry gives a resultant of times either phasor — a number that falls straight out of the rectangular subtraction shown in the derivation, specifically from .
Does the same root-3, 30-degree rule apply if the phase sequence is reversed, say R-B-Y instead of R-Y-B?
The magnitudes are unchanged — you still get and — but the sign of every angle flips, since reversing the sequence mirrors the whole phasor star. A line voltage that led its phase voltage by under R-Y-B will instead lag by under R-B-Y. Always redraw the phasor star for the sequence actually specified rather than assuming R-Y-B by default.
Is this root-3 rule specific to voltages, or does it apply to currents too?
It is a pure geometry result about subtracting two equal-magnitude phasors apart, so it applies to any such pair — voltages or currents. In a star connection it happens to relate phase and line voltages, because that is where the subtraction naturally occurs (line voltage is a difference of two phase voltages). In a delta connection the same subtraction occurs between winding currents, so it relates phase and line currents instead. The underlying algebra in the derivation above never assumed "voltage" — it works identically with in place of .