Transformer phasor diagrams

A transformer has no moving parts, yet everything inside it — flux, currents, EMFs — is a sinusoid chasing another sinusoid by some phase angle. Numbers alone (magnitudes of V1V_1, I1I_1, E2E_2...) cannot tell you whether the primary current leads or lags the applied voltage, or by how much, because that depends entirely on phase relationships that a bare list of magnitudes throws away. A phasor diagram is the tool that keeps magnitude and phase together in one picture. This node builds that picture in two stages: first on no-load, where the primary draws only a small magnetising/core-loss current I0I_0 with the secondary open, and then on full load, where a load current I2I_2 at some power factor is reflected back to the primary and combined with I0I_0. The mutual flux Φm\Phi_m is the natural reference phasor throughout, since it links both windings. By the end you should be able to resolve I0I_0 into its two components, sketch the full-load diagram for lagging and leading loads, and add phasors by rectangular components to get the actual primary current and its power-factor angle — which, perhaps surprisingly, is never quite equal to the load's own power factor.

The core insight

Taking the mutual flux Φm\Phi_m as reference, the no-load current I0I_0 splits into a magnetising component Iμ=I0sin⁡ϕ0I_\mu = I_0\sin\phi_0 (in phase with Φm\Phi_m) and a core-loss component Iw=I0cos⁡ϕ0I_w = I_0\cos\phi_0 (in phase with V1V_1), and on full load the primary current is the phasor sum I1=I0+I2′I_1 = I_0 + I_2' of this no-load current with the reflected load current, which is why the primary power factor is always slightly different from the secondary's.

The core idea

Why phasors, not just numbers. All quantities in a transformer — V1V_1, E1E_1, Φm\Phi_m, I0I_0, E2E_2, V2V_2, I2I_2 — oscillate at the same frequency but with different phase angles between them. A phasor diagram fixes one quantity as reference and draws every other quantity as an arrow at its correct angle relative to that reference, so magnitude and phase are both visible at a glance. The natural reference is the mutual (core) flux Φm\Phi_m, because it is the one quantity common to both the primary and secondary windings.

No-load current has two components. With the secondary open-circuited, the primary still draws a small current I0I_0 to set up the core flux and to supply the core (hysteresis + eddy-current) loss. Because E1E_1 leads Φm\Phi_m by exactly 90∘90^\circ (from Faraday's law) and V1≈−E1V_1 \approx -E_1 when the primary resistance/leakage drop is small, I0I_0 lags V1V_1 by an angle ϕ0\phi_0 that is close to but less than 90∘90^\circ. Resolving it along and perpendicular to V1V_1 gives:

Iw=I0cos⁡ϕ0,Iμ=I0sin⁡ϕ0I_w = I_0\cos\phi_0, \qquad I_\mu = I_0\sin\phi_0

where: IwI_w is the core-loss (working) component, in phase with V1V_1, supplying real power to core loss; IμI_\mu is the magnetising component, in phase with Φm\Phi_m (i.e. 90∘90^\circ behind V1V_1), producing the flux; ϕ0\phi_0 is the no-load power-factor angle. The two are related back to I0I_0 by I0=Iw2+Iμ2I_0 = \sqrt{I_w^2 + I_\mu^2}.

Full-load: reflect and add. On load, the secondary supplies current I2I_2 to the load at terminal voltage V2V_2 and power-factor angle ϕ2\phi_2 (lagging for inductive loads, leading for capacitive loads). E1E_1 and E2E_2 stay in phase with each other (both lead Φm\Phi_m by 90∘90^\circ), related by the turns ratio E1/E2=aE_1/E_2 = a. Referring the secondary current to the primary side, I2′=I2/aI_2' = I_2/a, the primary current is approximately the phasor sum

I1=I0+I2′I_1 = I_0 + I_2'

where: I0I_0 is the (unchanged) no-load current computed above, and I2′I_2' is the load current referred to the primary, at the same angle ϕ2\phi_2 relative to E2E_2 (hence to E1E_1) that the actual load current makes relative to V2V_2. Because I0I_0 is added vectorially, not scalar-added, I1I_1's magnitude is not simply I0+I2′I_0 + I_2', and its angle relative to V1V_1 is not exactly ϕ2\phi_2.

Lagging vs leading — the qualitative picture. For a lagging-pf load I2′I_2' lags E2E_2; since I0I_0 itself lags V1V_1 by nearly 90∘90^\circ, adding it typically nudges the overall lag angle of I1I_1 slightly beyond ϕ2\phi_2. For a leading-pf load I2′I_2' leads E2E_2, and the shift goes the other way. Either way, I1≈I2′I_1 \approx I_2' is a fair approximation only when I0≪I2′I_0 \ll I_2', which is the normal case for a transformer operating well above no-load.

Figure
Phasor diagram of a transformer on full load showing flux as reference with E1 E2 in phase leading it by ninety degrees and I0 I2 prime and I1 as their phasor sum at the lagging power factor angle
Full-load phasor diagram, lagging power factor flux Phi m E1, E2 I2 prime I0 I1 equals I0 plus I2 prime phi2
Derivation AEstimating the primary current by phasor addition

Given the no-load current I0I_0 at angle ϕ0\phi_0 behind the reference E1E_1, and the primary-referred load current I2′I_2' at angle ϕ2\phi_2 behind the same reference, find the magnitude and phase angle of the actual primary current I1I_1 by resolving both phasors into rectangular components and adding, since simply adding the two magnitudes arithmetically would ignore the fact that I0I_0 and I2′I_2' point in different directions and so cannot be summed like plain numbers.

Step 1. Write E1E_1 (or E2E_2, since they are in phase) as the reference phasor at angle 0∘0^\circ. Every other current is then expressed as a magnitude and an angle measured from this reference, lagging angles taken as negative.

Step 2. Resolve the reflected load current into rectangular form: I2′=∣I2′∣cos⁡ϕ2−j∣I2′∣sin⁡ϕ2I_2' = |I_2'|\cos\phi_2 - j|I_2'|\sin\phi_2, where the real part is the component in phase with E1E_1 and the imaginary part is the component 90∘90^\circ behind it (lagging, hence the minus sign for an inductive load).

Step 3. Resolve the no-load current the same way: I0=∣I0∣cos⁡ϕ0−j∣I0∣sin⁡ϕ0I_0 = |I_0|\cos\phi_0 - j|I_0|\sin\phi_0, using the no-load power-factor angle ϕ0\phi_0 measured from the same reference.

Step 4. Add the real parts and the imaginary parts separately, since rectangular components along the same axis add like ordinary numbers even though the underlying phasors do not: I1=(∣I2′∣cos⁡ϕ2+∣I0∣cos⁡ϕ0)−j(∣I2′∣sin⁡ϕ2+∣I0∣sin⁡ϕ0)I_1 = \left(|I_2'|\cos\phi_2 + |I_0|\cos\phi_0\right) - j\left(|I_2'|\sin\phi_2 + |I_0|\sin\phi_0\right).

Step 5. Recover the polar form from the summed rectangular components: ∣I1∣=(Re)2+(Im)2|I_1| = \sqrt{(\text{Re})^2+(\text{Im})^2} and ϕ1=tan⁡−1 ⁣(ImRe)\phi_1 = \tan^{-1}\!\left(\dfrac{\text{Im}}{\text{Re}}\right), which gives both the magnitude of the primary current and the angle by which it lags (or leads) V1V_1 — the actual primary power-factor angle, generally close to but not exactly equal to ϕ2\phi_2.

Worked example

A transformer's no-load current is I0=3 AI_0 = 3\,\text{A} at ϕ0=75∘\phi_0 = 75^\circ lagging the applied voltage V1V_1, and it supplies a load current I2′=40 AI_2' = 40\,\text{A} (referred to the primary) at a lagging power factor cos⁡ϕ2=0.8\cos\phi_2 = 0.8, so ϕ2≈36.87∘\phi_2 \approx 36.87^\circ. Find I1I_1.

Step 1 — resolve I0I_0 into components, in phase with V1V_1 and in phase with Φm\Phi_m respectively:

Iw=I0cos⁡ϕ0=3×cos⁡75∘≈0.776 A,Iμ=I0sin⁡ϕ0=3×sin⁡75∘≈2.898 AI_w = I_0\cos\phi_0 = 3\times\cos75^\circ \approx 0.776\ \text{A}, \qquad I_\mu = I_0\sin\phi_0 = 3\times\sin75^\circ \approx 2.898\ \text{A}

so in rectangular form I0=0.776−j2.898 AI_0 = 0.776 - j2.898\ \text{A} (check: 0.7762+2.8982≈3.0 A\sqrt{0.776^2+2.898^2}\approx 3.0\,\text{A} ✓ — as expected, the magnetising part dominates the small no-load current).

Step 2 — resolve I2′I_2' into components, lagging E1E_1 by 36.87∘36.87^\circ:

I2′=40cos⁡36.87∘−j40sin⁡36.87∘=32.0−j24.0 AI_2' = 40\cos36.87^\circ - j40\sin36.87^\circ = 32.0 - j24.0\ \text{A}

Step 3 — add the rectangular parts:

I1=(32.0+0.776)−j(24.0+2.898)=32.776−j26.898 AI_1 = (32.0+0.776) - j(24.0+2.898) = 32.776 - j26.898\ \text{A}

Step 4 — convert back to polar form:

∣I1∣=32.7762+26.8982=1074.3+723.5≈42.4 A|I_1| = \sqrt{32.776^2+26.898^2} = \sqrt{1074.3+723.5} \approx 42.4\ \text{A}
ϕ1=tan⁡−1 ⁣(26.89832.776)≈39.4∘ lagging\phi_1 = \tan^{-1}\!\left(\frac{26.898}{32.776}\right) \approx 39.4^\circ\ \text{lagging}

The primary current is I1≈42.4 A at 39.4∘ lagging\boxed{I_1 \approx 42.4\ \text{A at } 39.4^\circ \text{ lagging}} — slightly larger in magnitude and lagging by slightly more than the load's own 36.87∘36.87^\circ, because the no-load current's own lagging contribution adds a small extra lag.

Competitive stretch

If instead the same 40 A40\,\text{A} load were at a leading power factor of 0.80.8 (ϕ2≈36.87∘\phi_2 \approx 36.87^\circ leading), I2′I_2' becomes 32.0+j24.0 A32.0+j24.0\,\text{A}. Adding the same lagging I0=0.776−j2.898 AI_0 = 0.776 - j2.898\,\text{A} gives I1=32.776+j21.102 AI_1 = 32.776 + j21.102\,\text{A}, so ∣I1∣≈39.0 A|I_1|\approx 39.0\,\text{A} at about 32.7∘32.7^\circ leading — the primary angle shifts closer to unity power factor rather than further from it, showing the correction from I0I_0 works in opposite senses for lagging and leading loads.

Common traps

  • Treating I0I_0 as purely reactive (i.e. exactly 90∘90^\circ behind V1V_1): it always has a real, in-phase-with-V1V_1 component IwI_w that supplies core loss, so ϕ0\phi_0 is close to but strictly less than 90∘90^\circ.
  • Drawing E1E_1 in phase with Φm\Phi_m: they are 90∘90^\circ apart by Faraday's law, not aligned.
  • Assuming the primary power factor equals the secondary (load) power factor exactly: the phasor addition of I0I_0 shifts ϕ1\phi_1 away from ϕ2\phi_2, even if only slightly when I0≪I2′I_0 \ll I_2'.
  • Adding I0I_0 and I2′I_2' as plain magnitudes instead of rectangular components: this ignores their different phase angles and gives a wrong (too large) value for I1I_1.

Ask the tutor: If the rectangular-component phasor addition of I0I_0 and I2′I_2' still feels shaky, ask the AI tutor to redo the worked example with a leading-power-factor load of your own choosing and check your answer step by step.

Why do we pick the mutual flux Phi_m as the reference phasor instead of V1?

Because Φm\Phi_m is the one quantity common to both windings — both E1E_1 and E2E_2 are induced by it and both lead it by exactly 90∘90^\circ, so anchoring the diagram on Φm\Phi_m keeps the primary-side and secondary-side phasors tied together in one consistent picture. If you anchored on V1V_1 instead, you would still need to separately establish where Φm\Phi_m and hence E2E_2 sit relative to it, which is extra work for no benefit.

Is I1 = I0 + I2' an exact relationship or an approximation?

It is the standard approximate treatment used at this level, ignoring the (usually small) effect of primary leakage impedance drop on the phase relationship between I0I_0 and the flux that generates it, and treating I2′I_2' as referred by the simple turns ratio. In a fuller equivalent-circuit treatment (covered in the following topic) small corrections appear, but for phasor-diagram purposes this vector sum is accurate enough and is what you should use for problems and sketches at this stage.

Does the direction of the phase shift from I0 reverse between lagging and leading loads?

Yes. For a lagging load, I2′I_2' lags E2E_2, and adding the lagging I0I_0 tends to push I1I_1's angle slightly beyond ϕ2\phi_2 (more lag). For a leading load, I2′I_2' leads E2E_2, and adding the same lagging I0I_0 pulls the resultant angle back toward — or even past — the in-phase axis, as the competitive-stretch example above shows, shifting I1I_1 closer to unity power factor. The direction of the shift always depends on whether I0I_0 is adding to or partly cancelling the reactive part of I2′I_2'.