OC/SC tests and autotransformers
You cannot load a transformer to full rated power just to measure its losses — that wastes energy and risks the winding. Engineers instead run two short, cheap laboratory tests. The open-circuit (OC) test applies rated voltage with the far side left open, and reads off core loss and the magnetising-branch parameters. The short-circuit (SC) test applies just enough reduced voltage to push rated current through a shorted far side, and reads off copper loss and the series impedance. Together, at a combined input power of only a few percent of the transformer's rating, these two tests hand you every number needed for the equivalent circuit, and hence the regulation and efficiency at any load. This article works both tests through a single numerical transformer, then closes the unit with the autotransformer — a single tapped winding that trades away electrical isolation for a genuine saving in copper.
The OC test (rated voltage, secondary open) measures core loss and magnetising-branch parameters at negligible copper loss, the SC test (reduced voltage, secondary shorted, rated current) measures copper loss and series impedance at negligible core loss, and an autotransformer saves a fraction of winding copper by sharing part of the winding between primary and secondary at the direct cost of isolation.
The core idea
Why two separate tests, and not one. A transformer's losses split into core (iron) loss — nearly constant, set by flux and hence by applied voltage — and copper loss — proportional to current squared. No single test at one operating point can separate the two cleanly, because normal full-load operation has both rated voltage and rated current at once. The trick is to run two tests that each isolate one loss by starving the other of its driving quantity.
Open-circuit test. Rated (or near-rated) voltage is applied to one winding — usually the low-voltage side, since it needs less test-bench insulation — while the other winding is left open. With no secondary current, the primary draws only the small no-load current , so primary copper loss is negligible; almost the entire measured input power is core loss:
where: is core (iron) loss, is the no-load power-factor angle, and are the OC-test meter readings. Resolving along and perpendicular to splits it into the working component (feeds core loss) and the magnetising component (builds flux), from which and give the shunt magnetising-branch resistance and reactance.
Short-circuit test. The secondary is shorted, and only a small, reduced voltage is applied to the primary — just enough to drive rated current through the short. Because is a small fraction of rated voltage, the core flux (and hence core loss) at this test point is negligible; almost all the measured input power is copper loss at the test current:
where: are the equivalent series impedance, resistance and reactance referred to whichever side was energised in the SC test. If the test current equals full-load rated current, is the full-load copper loss directly — no scaling needed. Because the OC and SC tests are usually run on different sides for convenience, their results must be referred to a common side (via scaling of impedance) before being combined into one equivalent circuit.
Autotransformers. A two-winding transformer keeps primary and secondary as physically separate coils, isolated but each carrying its own full share of copper. An autotransformer instead uses one continuous, tapped winding: the section between the tap and the common terminal carries the load current shared by both sides, while only the remaining section carries the difference between primary and secondary current. Wherever current is shared rather than duplicated, less copper is needed for the same VA rating — the source of the autotransformer's economy, developed formally below.
Why it works
The goal is to show, from nothing more than the two-winding transformer's own copper requirement and the definition of turns ratio , that converting it into an autotransformer of the same voltage and VA rating saves a fraction of the winding copper — the formula already used in Worked example 2 below, derived here from first principles by counting how much copper each design needs to carry each ampere.
Step 1. Set up the two-winding baseline. For a transformer rated (primary), (secondary), full-load currents and , the copper needed is proportional to (turns current) for each winding, since a winding's volume of copper for a fixed current density scales with its total length of wire, i.e. its number of turns. Total two-winding copper is proportional to . Because (equal ampere-turns, from the transformer's own operating principle), this is in convenient units — write .
Step 2. Build the autotransformer with the same terminals. Use a single winding of turns between the 400 V terminal and the common point, tapped at turns from the common point for the 200 V terminal. The section from the tap to the common point ( turns) carries the difference current, by KCL at the tap, while the section from the 400 V terminal to the tap ( turns) carries only .
Step 3. Count autotransformer copper section by section. Series section: turns , current , contributing . Common section: turns , current , contributing (using ). Adding both sections: .
Step 4. Form the ratio against the two-winding baseline from Step 1. , using . So the autotransformer uses only a fraction of the two-winding copper, and the saving — the copper avoided — is the complement:
This confirms the result quoted in the core idea: the saving is largest when (the common section carries almost all the current, almost nothing is duplicated) and vanishes as (the tap shrinks to nothing and the design collapses back to two separate windings).
Worked example
A 20 kVA, 2000 V/200 V, 50 Hz transformer was tested: OC test (LV side energised) gave , , ; SC test (HV side energised, rated current) gave , , . Find the four equivalent-circuit parameters, and then estimate the copper this same transformer would save if it were rebuilt as an autotransformer of the same 2000 V/200 V ratio.
Step 1 — core loss and no-load branch (from the OC test). . The no-load power factor is , giving . The branch currents are and , so and (both referred to the LV side, where the OC test ran).
Step 2 — series impedance (from the SC test). , , and , all referred to the HV side, where the SC test ran. Since was the rated 10 A, is directly the full-load copper loss.
Step 3 — autotransformer copper saving at the same 2000 V/200 V ratio. Here , so from the boxed formula the saving is : rebuilding this particular transformer as an autotransformer of the same ratio would need only about a tenth of its present winding copper. That large a saving is unusual precisely because is far from 1 — it is why this specific transformer, with its 10:1 ratio, is a case where the autotransformer is copper-attractive but the loss of isolation between a 2000 V and a 200 V terminal would rule it out for most practical, safety-conscious uses.
Answer. ; , (LV side); , , (HV side); autotransformer copper saving at is 90 percent.
Common traps
- Mixing up which side each test is run on and forgetting to refer OC-side and SC-side parameters to a common side before combining them into one equivalent circuit.
- Assuming SC-test power directly equals full-load copper loss no matter what test current was used — it only holds when the SC test was run at rated current; otherwise scale by (current ratio).
- Treating the autotransformer copper-saving fraction as a saving in cost or loss rather than strictly a saving in winding copper quantity — core loss and other design factors are separate.
- Forgetting the tradeoff: the copper saving is real, but an autotransformer has no galvanic isolation between primary and secondary, which rules it out wherever isolation is a safety requirement.
Ask the tutor: if the referred-side scaling between OC- and SC-test parameters, or the step-by-step autotransformer copper-count in the derivation above, still feels shaky, ask the AI tutor to redo it with a fresh numeric example.
Why can't I just measure OC and SC test values on the same side of the transformer?
You often can, but test constraints usually push you the other way. OC voltage is applied at rated value, so it is more convenient on the low-voltage side; SC current must reach the rated full-load value, which is easier to source on the side with the larger winding current. The two tests often end up on different sides, so before combining from the OC test with from the SC test, refer them to one common side using the turns-ratio-squared scaling you already know from the ideal transformer.
Does a real autotransformer literally save 90 percent of copper the way the worked example shows for a equals 10?
The formula is correct arithmetic, but is an unusually large ratio for a practical autotransformer — most real applications (variacs, starting compensators, small step-up/step-down links) use ratios close to 1, precisely because that is where autotransformers are economical and the loss of isolation matters least. At you would be connecting a 2000 V circuit and a 200 V circuit on the same winding with no isolation, dangerous in most settings even though the copper saving is large — the formula tells you copper economy, not whether the design is a sound engineering choice.
If SC test current is not exactly the rated value, how do I still get full-load copper loss?
Copper loss scales with the square of current, . If the SC test ran at some current instead of rated , first find from as usual — that resistance does not change with current — then compute full-load copper loss as , or equivalently scale by . Only when already equals can you skip this and read off directly.